Quench Recovery Time Of An Optical Fiber Encapsulated Resistance-Type Dc Superconducting Fault Current Limiter Coil Determined By A Raman-Based Distributed Temperature Sensing System

SUPERCONDUCTOR SCIENCE & TECHNOLOGY(2021)

引用 6|浏览2
暂无评分
摘要
The superconducting fault current limiter (SFCL), as a very important power facility for high voltage DC system, can consume fault current energy and make DC breakers cut off fault transmission lines successfully. For the moment of reclosing DC breakers, the quench recovery time of the SFCL must be determined in advance. In this article, according to the design requirement of a 160 kV/1 kA resistance type DC SFCL in the Nan'ao multi-terminal flexible HVDC transmission demonstration project, the quench recovery time of a SCFL coil wound by two optical fiber encapsulated high temperature superconducting (OFE-HTS) tapes was checked by our optimized Raman-based distributed temperature sensing (Rm-DTS) system. The experimental results show that the used OFE-HTS tapes can withstand a 1500 A/100 ms AC short circuit current impact and are qualified with the SFCL. Furthermore, the quench recovery time of the SFCL coil measured by the Rm-DTS was 2930 ms. During the quench, the highest temperature zone occurred near the center of the SFCL coil.
更多
查看译文
关键词
distributed temperature sensing (DTS) system, optical fiber sensor, quench recovery time, Raman scattering, superconducting fault current limiter (SFCL)
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要