Bilinear observer-based robust adaptive fault estimation for multizone building VAV terminal units

JOURNAL OF BUILDING PERFORMANCE SIMULATION(2023)

引用 0|浏览0
暂无评分
摘要
In this paper, we propose a novel bilinear observer-based robust fault detection, isolation and adaptive fault estimation methodology to precisely estimate a class of actuator faults, namely bias in damper position and lock-in-place faults, in Variable-Air-Volume (VAV) terminal units of Heating Ventilation and Air-Conditioning (HVAC) systems. The proposed adaptive fault estimator is robust in the sense that the fault estimates are not affected by the unmeasured disturbance variable and that the effects of measurement noises on fault estimates are attenuated. The fault estimation algorithm with the integrated building control system improves occupants comfort and reduces the operation, maintenance, and utility cost, thereby reducing the impact on the environment. The effectiveness of the methodology for adaptive estimation of multiple or single VAV damper faults is successfully demonstrated through different simulation scenarios with SIMBAD (SIMulator of Building And Devices), which is being used in industries for testing and validation of building energy management systems.
更多
查看译文
关键词
Building automation, fault diagnosis, HVAC-VAV dampers, lock-in-place failure, bias fault, building energy efficiency
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要