Distance Protection for Lines Connecting Converter Interfaced Renewable Power Plants: Adaptive to Grid-end Structural Changes

IEEE Transactions on Power Delivery(2023)

引用 0|浏览6
暂无评分
摘要
Typical fault current characteristics of converter interfaced renewable power plants have significant impact on the reliability of traditional line distance protection. Large degrees of system non-homogeneity introduce substantial error in the apparent impedance calculation. In this paper, an adaptive distance relaying method for lines connected to converter-interfaced renewable power plants is proposed. A range of fault current phase angles is identified using the local and remote equivalent source impedances, which are calculated using only local measurements. Corresponding to the lower and upper bound of the identified range of fault current phase angle, two apparent impedances are calculated based on priority to dependability and security of protection operation. The trip decision is made based on the weighted sum of the first and second apparent impedances. Tuning of the dependability and security weightage factors based on the calculated remote grid-end source impedance, ensures adaptability and reliability of operation, even after structural changes in the grid. The proposed method is verified using IEEE 39 bus system and validated using field data. Comparative assessment with practically proven distance and modified distance protection method for lines connected with renewables is also provided.