In order to improve the grid-connected stability of wind power grid-connected inverter, solve the harmonic and resonance problems encountered at the grid-connected interface of inverter when the load jumps. An improved linear active disturbance rejection control strategy combined with active damping (ILADRC-AD) is designed. Firstly, the mathematical model of inductance-capacitance-inductance (LCL) inverter is established, and the principle of traditional third order active disturbance rejection controller is analyzed. Based on the idea of lead correction, an improved LADRC is designed by series lead correction links on the total disturbance channel of the linear extended state observer (LESO). Capacitive current feedback active damping is introduced in combination with improved LADRC to generate an ILADRC-AD control strategy. The stability and robustness of the system are effectively improved. Finally, the frequency characteristics of the ILADRC-AD inverter system are analyzed by frequency domain analysis method, and the MATLAB simulation comparison of improved control and traditional PI and LADRC the grid current waveform. The results show that the improved control not only has more stable grid-connected current, but also has fast dynamic response and strong harmonic suppression when the load fluctuates.