An On-Line Real-Time Monitoring Method for Locating Natural Triggered Events on Medium Voltage Power Grids

2020 XXXIIIrd General Assembly and Scientific Symposium of the International Union of Radio Science(2020)

引用 0|浏览2
暂无评分
摘要
Time reversal (TR) has been recently adapted with success to locate faults in power grids, thanks to its location accuracy and robustness against parameters uncertainties. FasTR algorithm, a post-processing approach based on the tenets of TR, has shown promising results in locating disturbances along transmission line networks. This paper presents the outcome of tests performed on a 2.6 km energized three-phase 20 kV buried pilot network. The tests involve single-phase-to-ground fault occurrences manually triggered, and a 3-month real-time continuous monitoring while the network is in normal operation. The fault location task is performed by a system composed four components: distributed high-speed measurement devices, accurate time synchronization, a communication tool between sensors and the FasTR post-processing algorithm. The obtained results demonstrated the capacity of an on-the-shelf portable system to make an on-line accurate detection of transient faults in a complex network.
更多
查看译文
关键词
real-time monitoring method,natural triggered events,medium voltage power grids,time reversal,transmission line networks,single-phase-to-ground fault,fault location,high-speed measurement devices,accurate time synchronization,FasTR post-processing algorithm,on-the-shelf portable system,transient faults,complex network,buried pilot network,communication tool,size 2.6 km,voltage 20.0 kV