An experimental study on refrigerant distribution in a two row/four pass parallel flow minichannel heat exchanger

Heat and Mass Transfer(2015)

引用 4|浏览7
暂无评分
摘要
R-410A distribution was experimentally studied for a parallel flow evaporator having two row/four pass configuration. The evaporator has inlet, intermediate and row-crossing headers. Tests were conducted for the mass flux from 70 to 130 kg/m 2 s with the quality at the inlet of 0.2 and exit superheat 5 °C. Significant heat transfer degradation (13–40 %) was realized for the two row/four pass configuration due to flow mal-distribution. Of the three insert hole sizes, 4.0 mm hole yielded the least heat transfer degradation followed by 6.0 and 2.0 mm holes. At the inlet header, more liquid flowed into upstream channels. At the intermediate headers, more liquid was supplied into downstream channels. Similar flow distribution was obtained before and after the row crossing header. Header pressure drops were obtained by subtracting the flat tube pressure drops and other minor pressure drops from measured pressure drops.
更多
查看译文
关键词
Pressure Drop,Mass Flux,Vapor Quality,Round Tube,Flat Tube