Detection of Series Arcs in Low-Voltage AC Power Lines Using Load Side Voltage Sag and Waveform Similarity Comparison

IEEE ACCESS(2024)

引用 0|浏览2
暂无评分
摘要
The similarity between arc fault current waveforms and nonlinear load currents can lead to misjudgments in arc fault identification methods that rely on arc current. In response to this issue, this paper establishes a unified fault criterion based on the conclusion that different types of loads that exhibit similar magnitudes of load side voltage sag during arc faults. Combined the voltage sag criterion with waveform criteria, this paper proposes a novel arc fault detection method. The method takes the load side voltage sag value exceeding the threshold as the detection start condition. After detection starts, the method identifies faults by calculating the degree of load side voltage waveform distortion using Hausdorff distance algorithm. Simulations are conducted on five different loads to determine the startup threshold and detection threshold. Test results show that the fault identification accuracy of the proposed method is 100% under the above thresholds.
更多
查看译文
关键词
Series arc fault,arc voltage,voltage sag,Hausdorff distance
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要