The energy performances of an elastocaloric device for air conditioning through numerical investigation

Applied Thermal Engineering(2024)

引用 0|浏览0
暂无评分
摘要
•A rotary prototype for air conditioning based on elastocaloric effect is introduced.•A 2D rotative numerical model has been used to design the prototype.•A map of the energy performances under variable operating conditions is presented.•28.5 K and 5400 W kg−1 are the achievable peaks of temperature span and cooling power.•6.22 is the maximum coefficient of performance weighted as 60% of II law efficiency.
更多
查看译文
关键词
Elastocaloric effect,Rotary model,Multiphysics simulations,Thermo-fluidodynamic model,Energy performances