A modified 72-pulse rectifier for harmonic suppression in more electric aircraft applications

IEEE Transactions on Transportation Electrification(2023)

引用 0|浏览0
暂无评分
摘要
A parallel-connected 72-pulse rectifier (72PR) based on a 36PR with a passive harmonic mitigation method (PHMM) is proposed for harmonic mitigation in more electric aircraft applications. The PHMM is connected to the 36PR DC-side and consists of two harmonic reduction circuits (HRCs) and contains a four-tapped interphase reactor (FTIR) and four auxiliary diodes. Since the proposed design only requires a low-capacity PHMM (about 0.23% of the load power) and does not need any switching and control circuits, therefore; the proposed 72PR is a modified and low-cost solution. On the other hand, by using the proposed circuit, the input current is almost sinusoidal and its input current total harmonic distortion (THD) is less than 1%, which meets the IEEE-519 standard. In addition, the input current harmonic components at 400Hz-800Hz are less than the requirements mentioned in the DO-160G standard without using any input and output filters. Also, in all types of diode open-circuit faults, the proposed improved 72PR shows more fault-tolerant behavior and better performance in THD reduction. In the paper, the effectiveness of the proposed 72PR in reducing harmonic distortion is confirmed, using simulation and experimental results.
更多
查看译文
关键词
72-pulse rectifier (72PR),Passive harmonic mitigation circuit (PHMM),Four tapped interphase reactor (FTIR),Harmonic suppression circuit (HRC),Diode open-circuit fault