Study on Noise Source Contribution of Converter Cabinet Based on Transfer Path Analysis Test

Li Fan, Jian Zhang, Fan Yi, Xiaowei Zhang,Qi Li

Journal of physics(2023)

引用 0|浏览0
暂无评分
摘要
There are fan noise and transformer noise sources inside the converter cabin which may bring the environmental noise pollution through airborne or structural borne paths. In order to identify the contribution of each source and its path, transfer path analysis test was performed. Take full load working condition at full speed as an example, the contributions of fan air borne noise, fan structural borne noise, transformer air borne noise and transformer structural borne noise are 88.33%, 3.79%, 7.37% and 0.51% respectively. The contribution of air borne noise is 95.70% more than that of structural borne noise which is 4.30%. In the end the aerodynamic noise simulation of converter cabin is compared with the experimental result which is in good coincidence, this result can also verifies the noise source contribution result.
更多
查看译文
关键词
converter cabinet,transfer path analysis test,noise source contribution