Power Supply Reliability Analysis of Distribution Systems Considering Data Transmission Quality of Distribution Automation Terminals

Fengzhang Luo, Nan Ge, Jing Xu

ENERGIES(2023)

引用 0|浏览1
暂无评分
摘要
A distribution automation system is the integration of physical power distribution systems and information systems. Its information system guarantees the safe operation and reliable power supply of physical systems by monitoring, collecting and transmitting information. In the information system, the remote terminal unit of distribution automation is the hub of the information system, connecting it to the physical power system. Considering the unreliability of terminal information transmission in the information system, this paper aims to build a model to quantitatively evaluate the impact of unreliable transmission information on the power supply reliability of distribution systems. Firstly, the m-segment and n-connection unit model of distribution feeders is established, and then, the power supply reliability indices in the process of handling feeder terminal unit error are analyzed and calculated under the configuration modes of "three-remote" and "two-remote" of remote terminals. Then, considering the impact of a transmission error in the information system, the reliability index calibration model under the condition of unreliable information transmission is established. Finally, a case study is presented to illustrate how the proposed model is implemented.
更多
查看译文
关键词
distribution automation system,power supply reliability,remote terminal unit,unreliable information transmission
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要