Risk-Aware Operating Regions for PV-Rich Distribution Networks Considering Irradiance Variability

IEEE Transactions on Sustainable Energy(2023)

引用 0|浏览0
暂无评分
摘要
This article proposes a framework to identify, visualize, and quantify risk of potential over/under voltage due to annual energy consumption and PV generation growth. The stochastic modeling considers the following: (i) Active and reactive power profiles for distribution transformers, dependent on annual energy consumption and activity in the serviced areas. (ii) Variable solar irradiance profiles that allow a broader range of PV generation scenarios for sunny, overcast, and cloudy days. The proposed framework uses multivariate- $t$ copulas to model temporal correlations between random variables to generate synthetic scenarios. A probabilistic power flow is computed using the generated scenarios to define critical static operating regions. Results show that classical approaches may underestimate the maximum PV capacity of distribution networks when local irradiance conditions are not considered. Moreover, it is found that including annual energy consumption growth is critical to establishing realistic PV installation capacity limits. Finally, a sensitivity analysis shows that taking a 5% of overvoltage risk could increase up to 15% of the PV installed capacity limits.