Experimental and numerical investigation on thermal performance of data center via fan-wall free cooling technology
Applied Thermal Engineering(2023)
摘要
•A fan wall data center (DC) test platform was established.•Explored the influence of heat dissipation power and ventilation parameters.•Ventilation rate of 0.5 m3/s is suitable for a 2.5 kW rack considering the ventilation temperature of 27 °C.•A supply air volume (SAV) model was obtained and validated for fan-wall DCs.•According to the SAV model, approximately 34% energy consumption of fans will be saved for fan-wall DCs located in Guiyang.
更多查看译文
关键词
Data centers,Fan wall cooling,Thermal environment,Free cooling,Energy saving