The Influence of Heat Transfer Coefficient alpha of Insulating Liquids on Power Transformer Cooling Systems

ENERGIES(2023)

引用 0|浏览4
暂无评分
摘要
The power transformer plays an important role in electric power systems. One of the conditions for the proper operation of the transformer is to ensure a sufficiently low temperature. This condition can be met if the heat exchange is effective. Heat transfer depends, among other things, on the electrically insulating liquid. The thermal property describing the ability of a liquid to transfer heat is the heat transfer coefficient alpha. At the design stage of the transformers, it is most often assumed that the value of the alpha coefficient is constant and equal to 100 W center dot m(-2)center dot K-1. Such simplifications can lead to the improper design of the transformer since this factor depends on many factors. The article presents the results of research on the dependence of the heat transfer coefficient alpha on the type of electrical insulation liquid, the thermal load of the cooled surface, and the length of the heating element. Four types of electrical insulating liquids were considered: mineral oil, synthetic ester, natural ester, and natural ester with reduced viscosity. The obtained results prove that the type of electrical insulating liquid and the thermal surface load value affect the alpha coefficient. The length of the heating element did not affect the alpha factor.
更多
查看译文
关键词
power transformers, insulating liquid, temperature distribution, heat transfer