Propagation of Supraharmonics in a Data Center With Different Operating Modes of UPS

IEEE Access(2023)

引用 0|浏览1
暂无评分
摘要
A data center is a major hub of different converters ensuring continuous power to the server loads. The pulse width modulation switching techniques with frequency emission from 2 to 150 kHz (i.e., supraharmonics) in these converters call for a study of the magnitude and propagation of this emission within data centers where UPS is one of the main contributors of supraharmonics. The paper shows, with measurements and model, the change in magnitude and propagation of supraharmonics with the change in the operating mode of the UPS. The magnitude of supraharmonics shows a non-linear dependency on the power consumed in the online mode. In bypass mode, the magnitude of supraharmonics shows a dependency on the type of load connected. The filter connected between PE-N at the input side of the UPS can cause resonance in the phase conductors. The results show that to study the emission, immunity, and electromagnetic compatibility of supraharmonics for UPS, the factors such as operating mode, the type of load connected, and the input and output impedance need to be considered.
更多
查看译文
关键词
Data center,electromagnetic compatibility,power quality,power conditioning,uninterruptible power supply,pulse width modulation