Testing Ground Fault Protection of Generating Units With Frequency-Selective Grounding

IEEE Transactions on Industry Applications(2023)

引用 3|浏览4
暂无评分
摘要
This paper experimentally evaluates responses of ground fault protection for synchronous generators, which are grounded using frequency-selective grounding. Frequency-selective grounding is designed to provide a low ground impedance path (similar to solid grounding) for high frequency zero-sequence current components. This grounding system also provides an impedance similar to a low-resistance grounding for low frequency zero-sequence current components. The frequency-dependent equivalent impedance of frequency-selective grounding can affect ground potential and current, which are typically used as inputs for ground fault protective relays. Effects of frequency-selective grounding on ground fault protection are experimentally evaluated using a 7.5 kVA synchronous generator. Experimental tests are conducted for different implementations of ground fault protection, when responding to fault and non-fault events. Evaluation results detailed in this paper demonstrate the negligible effects of frequency-selective grounding on responses of different ground fault protective relays.
更多
查看译文
关键词
Frequency-selective grounding,power system faults,and ground fault protection of synchronous generators