Study on the Lightning Protection Performance for a 110 kV Non-Shield-Wired Overhead Line with Anti-Thunder and Anti-Icing Composite Insulators

Energies(2023)

引用 1|浏览4
暂无评分
摘要
Due to micro landforms and climate, the 110 kV transmission lines crossing the mountain areas are exposed to severe icing conditions for both their high voltage (HV) conductors and shield wires during the winter. Ice accumulation on the shield wire causes excessive sag, which leads to a reduced clearance between earth and HV wires, and could eventually result in tripping of the line due to phase-to-ground flashover. Due to the lack of effective de-icing techniques for the shield wires, removing them completely from the existing overhead line (OHL) structure becomes a reasonable solution to prevent icing accidents. Nevertheless, the risk of exposure to lightning strikes increased significantly after the shield wires were removed. In order to cope with this, the anti-thunder and anti-icing composite insulator (AACI) is installed on the OHLs. In this article, the 110 kV transmission line without shield wire is considered. The shielding failure after installation of the AACIs is studied using the lightning strike simulation models established in the ATP software. The lightning stroke flashover tests are carried out to examine the shielding failures on various designs for the AACIs. Assuming the tower’s earth resistance is 30 Ω, the LWL of back flashover and direct flashover are 630.88 kA and 261.33 kA, respectively, after the installation of AACIs on an unearthed OHL. Due to the unique mechanism of the AACI, the operational voltage level and the height of the pylon have a neglectable influence on its lightning withstand level (LWL). When the length of the parallel protective gap increases from 450 mm to 550 mm, the lightning trip-out rate decreases from 0.104 times/100 km·a to 0.014 times/100 km·a, and the drop rate reaches 86.5%. Therefore, increasing the gap distance for the AACI to provide additional clearance is proven to be an effective method to reduce the shielding failure rates for non-shield-wired OHLs.
更多
查看译文
关键词
non-shield-wired overhead lines,anti-thunder and anti-icing composite insulator,lightning withstand level,shielding failure,parallel clearance,lightning trip rate
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要