Equivalent model for interconnected power systems based on sensitivity consistency of tie-line power

Energy Reports(2023)

引用 0|浏览3
暂无评分
摘要
Static security analysis (SSA) is a significant measure to verify the secure and stable operation of power grids. However, it is too time-consuming to perform SSA for interconnected networks due to the scale of network. Therefore, the equivalent-based method attracts attention due to simplifying the external networks (uninteresting networks). However, existing equivalent methods are not suitable for SSA, which are based on the assumption that the topology of internal networks is invariant. This paper proposes a novel static network equivalent method for SSA in interconnected networks. The proposed method can adaptively and precisely preserve the impact of external networks on topology changes of internal networks. Specifically, based on the sensitivity consistency of tie-line power, the equivalent nodal admittance matrix is derived for the external networks. The parameters for the obtained equivalent networks are obtained by least square model with Kirchhoff and necessary logistic constraints to achieve the optimal equivalence accuracy. The accuracy and practicability of proposed method are verified by using IEEE 39-bus system and IEEE 118-bus system. (c) 2023 The Authors. Published by Elsevier Ltd. This is an open access article under the CC BY-NC-ND license (http://creativecommons.org/licenses/by-nc-nd/4.0/).
更多
查看译文
关键词
Static safety analysis,Sensitivity consistency of tie-line power,Static network equivalent method,The external networks,Accuracy and practicability
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要