New Selective Directional Ground Fault Protection Method for Ungrounded Systems

IEEE Transactions on Power Delivery(2022)

引用 1|浏览0
暂无评分
摘要
Ground faults are the main cause of electrical failure in transmission and distribution systems. In ungrounded distribution networks, it is difficult to detect where a first ground fault has happened as only capacitive currents are available. Also, it is important to trip only the faulty line in order to ensure the system's reliability. Directional residual overcurrent relays are the standard solution for these systems, but their difficult commissioning and high costs make it not trivial. This paper introduces a new selective and directional protection method to determine the faulty line in ungrounded medium voltage networks with three or more feeders. The method evaluates the residual currents in the feeders coupled to the same busbars in combination with a reference current created by the sum of a combination of residual currents of all feeders. Both simulation and laboratory results validate this new method, which is easy to start up, as it does not need previous configurations for its implementation, and it presents an economical solution to this problem.
更多
查看译文
关键词
Current transformers,fault protection,power distribution,power distribution faults,power system protection,relays