Thermal performance of a non-segmented and segmented tall atrium in hot and humid climate

CARBON-NEUTRAL CITIES - ENERGY EFFICIENCY AND RENEWABLES IN THE DIGITAL ERA (CISBAT 2021)(2021)

引用 0|浏览0
暂无评分
摘要
The study was designed to quantify the thermal conditions in tall atria in office buildings to serve as a starting point towards understanding their performance. The simulation study of a non-segmented and segmented atrium of 250 m height reveals indoor air temperature, wind velocity contours and wind pressure coefficients at various heights of each atrium type. In a hot and humid climate like that of Singapore, the internal temperatures within each atrium stack remain constant at 27 degrees C. However, the wind velocity in the non-segmented atrium (of 0.5 - 0.7 m/s) is lower than acceptable (0.9 m/s) for human occupancy. Adding segments and a larger inlet to the atrium solves the problem of low wind velocity without increasing the effective ambient temperature within the atrium stack. Additionally, the segmented atrium offers the advantage of displaying lower buoyancy forces by lowering the pressure differential within a tall stack thereby providing better comfort conditions.