A New Backup Protection Scheme for Transmission Lines with Limited Phasor Measurement Units

ELECTRIC POWER COMPONENTS AND SYSTEMS(2022)

引用 0|浏览0
暂无评分
摘要
This paper proposes a new scheme for backup protection of transmission lines with a limited number of phasor measurement units (PMUs). In the presented methodology, the PMUs are located (or installed) in accordance with a scheme allowing all faults to be observable. The network is divided into a few zones with 1, 2 or 3 transmission lines. Following this, the nearest bus to the fault location, named as the faulted bus, is selected through the voltage data measured by PMUs. A faulted area including the suspected zones, the zones connected to the faulted bus, is then identified. The faulted zone is subsequently recognized by using the phase deviation between the positive-(negative-) sequence voltage of the faulted bus and the positive-(negative-) sequence of the input current to the suspected zones. The faulted line is finally detected based on the type of the faulted zone and corresponding algorithm. The effectiveness of the presented scheme is assessed under several fault situations in MATLAB/Simulink platform. Simulation results demonstrate that the proposed method detects the faulted line accurately for all fault conditions. Moreover, the proposed scheme protects the shunt-compensated transmission lines as properly as the uncompensated ones without using the pre-fault data.
更多
查看译文
关键词
phasor measurement unit (PMU), limited PMUs, wide area backup protection (WABP), faulted bus, faulted area, faulted zone, zone_type, faulted line, shunt-compensated line