Experimental investigation of flow characteristics in a vertical vibration two-phase loop thermosyphon

Thermal Science(2022)

引用 0|浏览1
暂无评分
摘要
In this paper, flow characteristics of a two-phase loop thermosyphon under vertical reciprocating vibration are visually investigated with N-pentane as the working fluid. The tests are performed for a heating power range of 20 W to 40 W, the filling ratio of 30 % to 70%, and a 30 m•s-2, 35 Hz vertical reciprocating vibration. The effect of vertical vibration on flow characteristics of the two-phase loop thermosyphon is investigated by comparing the obtained results with those acquired in static, thereby providing a basis for explaining the heat transfer process of two-phase loop thermosyphon under vibration. The results indicate that vertical vibration promotes the rupture of a liquid plug and the transformation of the plug flow to annular flow or wavy flow. Furthermore, the vertical vibration does not change the distribution law of liquid flow velocity in the two-phase loop thermosyphon. However, it will reduce the overheating and flow velocity in the two-phase loop thermosyphon at the start-up. With an increase in the heating power, the influence of vertical vibration on liquid flow velocity is reduced due to continuous disturbance of the working medium in the two-phase loop thermosyphon.
更多
查看译文
关键词
two-phase loop thermosyphon, vertical vibration, flow characteristic, visualization