Magnetic Flux Control In An Urban Distribution Network Based On Load Optimisation
PROCEEDINGS OF THE INSTITUTION OF CIVIL ENGINEERS-ENERGY(2021)
摘要
This paper proposes a control method for eliminating direct current (DC) flux from the isolation transformer of a customer service device to avoid magnetic saturation. The method is characterised by injecting zero compensation voltage during a designed time. The period during which no compensation voltage is injected is minimised by adjusting the normal compensation time in the initial stage. For a customer service device, such as a dynamic voltage restorer, the reverse turn-off voltage will introduce extra initial flux. The calculation process based on a trigonometric function also takes into account the effects of the initial flux. The experimental results verify the proposed method to prevent DC flux to the isolation transformer.
更多查看译文
关键词
electrical engineering & distribution, energy conservation, power
AI 理解论文