A New Checking Method of CT Polarity for Transformer Zero-sequence Differential Protection

Maolin Wang,Xianggen Yin,Wenbin Cao,Yuanlin Pan, Maoran Zheng, Jingwei Zhang

2020 5TH ASIA CONFERENCE ON POWER AND ELECTRICAL ENGINEERING (ACPEE 2020)(2020)

引用 0|浏览1
暂无评分
摘要
Zero-sequence differential protection is one of the foremost protections for EHV and UHV power transformers due to the advantages of high sensitivity and fast operation speed. The precondition of its correct operation is the correct CT polarity, but the checking of its CT polarity requires large zero-sequence current. However, there is almost no zero-sequence current during normal operation of transformer, which makes it difficult to carry out CT polarity checking of zero-sequence differential protection. To solve this problem, a new checking method of CT polarity for zero-sequence differential protection is proposed in this paper. First, calculate the similarity (S and F) between the self-produced zero-mode inrush current (3I 0p ) and the current of neutral point (3I 0n ). Second, compare the similarity (S and F) with the setting values determined in this paper. Third, assume different error types of CT polarity and reverse the corresponding CT current. Fourth, recalculate the similarity (S and F) in different error types and get the the maximum value of S and the corresponding F (S max and F m ). Finally, repeat step 2 and the error type corresponding to the S max and F m can be identified. This method is verified by digital simulation in this paper. The results show that this method can accurately identify all error types of CT polarity under different working conditions.
更多
查看译文
关键词
zero-sequence differential protection, CT polarity, checking method, similarity, zero-mode inrush current
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要