Residual Charges on Barrier Surface Revealed by Potential Distribution in a Hybrid Gas-Solid Insulation System

ieee international conference on high voltage engineering and application(2020)

引用 1|浏览0
暂无评分
摘要
The characteristics of residual charges on the inserted barrier surfaces in different air-insulated insulation systems after alternating breakdowns are investigated. High voltage withstand tests and surface potential measurements were carried out. The results show that the potential polarity on the barrier surface is related to the voltage polarity at the moment of breakdown. The barrier surface potential where the discharge passes through is lower. Compared with the barrier position, the electrode radius has a more significant effect on the surface potential distribution after breakdown. As the electrode radius increases, the positive surface potential is higher and the area with the potential higher than 3 kV is larger. The surface potential decays slowly when the barrier is suspended. At last, the effect of residual charges revealed by the surface potential is discussed.
更多
查看译文
关键词
hybrid insulation,barrier effect,residual charge,air insulation,breakdown voltage