Modeling and Stability Analysis of Weak-Grid Tied Multi-DFIGs in DC-Link Voltage Control Timescale

ENERGIES(2020)

引用 4|浏览17
暂无评分
摘要
The DC-link voltage control (DVC) timescale (i.e., the frequency dynamics covering converter outer controls) instabilities in wind generation have gained increased attention recently. This paper presents DVC timescale modeling and stability analysis for multi doubly-fed induction generators (DFIGs) connected to weak AC grids. A reduced-order, small-signal model of a grid-tied multi-DFIG system, designed for DVC dynamics analysis, is firstly proposed. The model allows for the dynamic interactions among the DC-link voltage control, active power control (APC), terminal voltage control (TVC) and phase-locked loop (PLL). Eigenvalue and participation factor analyses are conducted to explore the potential instabilities and correlated critical factors for such a multi-machine system. The sensitivity studies find that instability can occur at high levels of power generations or low short-circuit ratio (SCR) conditions. In addition, the dominant mode is identified to be highly related to the PLL, and its modal damping is decreased when the bandwidths of PLLs in different generators are close. Detailed model-based time domain simulations verified the analysis above.
更多
查看译文
关键词
DFIG,weak grid,DC-link voltage control timescale,eigenvalue analysis,PLL
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要