Effects of Evaporator and Condenser in the Analysis of Adsorption Chillers

ENERGIES(2020)

引用 4|浏览4
暂无评分
摘要
In a survey of the literature from the last 20 years, 20% of the numerical models used to analyze the performance of adsorption chillers assumed the evaporator and condenser were ideal, with a fixed evaporation temperature and condenser temperature, and ignored interactions between the adsorption bed and evaporator/condenser. Even when the interaction with the evaporator and condenser was included, the other 80% of studies modeled the adsorption bed based on the LPM (lumped parameter method), which ignores the geometry effect and contact resistance of the bed, and thus reduces the accuracy of the analysis. As a consequence, these earlier numerical studies overestimated the system performance of the adsorption chiller. In this study, we conducted a refined numerical approach which avoids these limitations, producing estimates in close agreement with experimental results. Compared with our approach, the models with ideal treatment of evaporator and condenser overestimated COP (coefficient of performance) and SCP (specific cooling power) by as much as 16.12% and 24.64%, respectively. The models based on LPM overestimated COP and SCP by 22.82% and 11.28%, compared to our approach.
更多
查看译文
关键词
adsorption chiller,numerical analysis,evaporator,condenser