Effect of sensor position on the performance of CO2-based demand controlled ventilation

Energy and Buildings(2019)

引用 39|浏览7
暂无评分
摘要
•CO2 sensors near occupants result in large errors under displacement ventilation.•CO2 sensors at breathing height perform well for constant occupancy conditions.•CO2 sensors at breathing height yield errors with varying occupancy.•Under mixing ventilation, CO2 sensors at the room exhaust yield a good accuracy.
更多
查看译文
关键词
Indoor air quality,CO2 sensing,Computational fluid dynamics,Building energy,Displacement ventilation
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要