Effect of sensor position on the performance of CO2-based demand controlled ventilation
Energy and Buildings(2019)
摘要
•CO2 sensors near occupants result in large errors under displacement ventilation.•CO2 sensors at breathing height perform well for constant occupancy conditions.•CO2 sensors at breathing height yield errors with varying occupancy.•Under mixing ventilation, CO2 sensors at the room exhaust yield a good accuracy.
更多查看译文
关键词
Indoor air quality,CO2 sensing,Computational fluid dynamics,Building energy,Displacement ventilation