Fault Overload Control Method for High-Proportion Wind Power Transmission Systems Based on Emergency Acceleration of Doubly-Fed Induction Generator.

IEEE ACCESS(2019)

引用 7|浏览11
暂无评分
摘要
With a high proportion of wind power being transmitted through ac and dc lines, a new power grid pattern has gradually emerged. A dc inverter is prone to commutation failure, which may lead to cascading trip of ac lines for overload, resulting in serious consequences. However, existing control methods have problems of over-or under-shedding and are unsuitable for high-proportion wind power transmission systems. Accordingly, a new fault overload control method based on emergency acceleration of doubly fed induction generator (DFIG) is proposed. The fast power control capability of DFIG is fully utilized; the active power of power grid could be rapidly balanced. First, the fault characteristics of a wind power ac/dc transmission system under the fault of dc receiving-end grid are analyzed, and the power flow transfer after self-recovery from the dc commutation failure is derived. Second, by analyzing the power characteristics of DFIG, a fault overload control idea of the wind power transmission system is proposed based on emergency acceleration of DFIG. At last, the maximum controllable capacity of a wind farm is analyzed, and a fault overload control strategy of the wind power transmission system is proposed. The simulation results prove that the proposed method can rapidly reduce the output of wind farms and prevent the overload of ac lines.
更多
查看译文
关键词
AC/DC system,DFIG-based wind farm,power flow transfer,cascading trip,emergency power control