Error analysis of capacitor voltage transformer in the operation environment

2016 IEEE International Conference on High Voltage Engineering and Application (ICHVE)(2016)

引用 5|浏览7
暂无评分
摘要
The capacitor voltage transformer (CVT) is a potential transformer (PT) composed of capacitive voltage divider and electromagnetic unit. In high voltage classes, the capacitor voltage transformer has the advantage of simpler structure and lower cost in comparison with electromagnetic potential transformer (PT), so potential transformers with voltage class of 220kV and above are CVT basically. Transformer acts as an important link of power trade measuring system, and its accuracy is directly related to the justness and fairness of power trade. CVT at transformer substation is usually installed outdoor and often runs in different natural environments, while periodic detection is adopted for CVT, but there is no relevant research on the impacts of CVT error characteristics from the natural environment during actual operation. In this paper, online monitoring system is used to compare a good-stability bus with line CVT, taking PT as standard, so as to research the CVT error characteristics in actual operation cases. As the result indicated, ratio error and angle error of the CVT present regular changes within 24h, two extreme inflection points of the ratio error respectively occur at 6:00 a.m. and 4:00 p.m., representing shifting towards negative values, similar phase errors, but no out-of-tolerance.
更多
查看译文
关键词
Capacitor voltage transformer,Online monitoring,Error,Accuracy,Inflection point