A new LPF-based grid frequency estimation for the SOGI filter with improved harmonic rejection

J. Matas,Helena Martín, J. Elmariachet,Abdullah Abusorrah, Y. Al-Turki

Renewable energy & power quality journal(2018)

引用 5|浏览19
暂无评分
摘要
This paper proposes a new method for the estimation of the grid voltage frequency using a low-pass filter (LPF) approach. The estimated frequency is used to tune a second order generalized integrator (SOGI) filter commonly used for grid monitoring purposes and applications requiring parameter estimation from the grid. A first-order LPF is used first for the estimation that behaves identically to the reported normalized SOGI-FLL. A second-order LPF is proposed instead to overcome this circumstance. The behavior of this approach is dynamically analyzed and a linearized model useful for design purposes is derived. The behavior of the proposed system is checked with simulations, showing that the model matches well with the real system and has a smoother transient response to step frequencyperturbations and also a better rejection to harmonic distortion than previous approaches.
更多
查看译文