Review of the Accuracy of Single Core Equivalent Thermal Model for Offshore Wind Farm Cables

IEEE Transactions on Power Delivery(2018)

引用 19|浏览5
暂无评分
摘要
Cables intended to interconnect offshore wind farms with the mainland are currently treated as separate lead-type cables by IEC 60287. A single core equivalent thermal model (SCETM) is implied, that is, a thermal model accounting for 1-D (radial) heat transfer only. While this approach is expected to be reasonable when smaller cables are rated, the 1-D representation is less valid in larger cable ...