Boric Acid Corrosion of Concrete Rebar

EPJ Web of Conferences(2013)

引用 5|浏览2
暂无评分
摘要
Borated water leakage through spent fuel pools (SFPs) at pressurized water reactors is a concern because it could cause corrosion of reinforcement steel in the concrete structure and compromise the integrity of the structure. Because corrosion rate of carbon steel in concrete in the presence of boric acid is lacking in published literature and available data are equivocal on the effect of boric acid on rebar corrosion, corrosion rate measurements were conducted in this study using several test methods. Rebar corrosion rates were measured in (i) borated water flowing in a simulated concrete crack, (ii) borated water flowing over a concrete surface, (iii) borated water that has reacted with concrete, and (iv) 2,400 ppm boric acid solutions with pH adjusted to a range of 6.0 to 7.7. The corrosion rates were measured using coupled multielectrode array sensor (CMAS) and linear polarization resistance (LPR) probes, both made using carbon steel. The results indicate that rebar corrosion rates are low (similar to 1 mu m/yr or less) when the solution pH is similar to 7.1 or higher. Below pH similar to 7.1, the corrosion rate increases with decreasing pH and can reach similar to 100 mu m/yr in solutions with pH less than similar to 6.7. The threshold pH for carbon steel corrosion in borated solution is between 6.8 and 7.3.
更多
查看译文
关键词
corrosion,concrete