Decompression cooling system operation for HTS power cable in the KEPCO power grid

ADVANCES IN CRYOGENIC ENGINEERING(2014)

引用 4|浏览8
暂无评分
摘要
A 3-phase 22.9 kV/50 MVA 410 m HTS power cable system was installed at power grid of KEPCO and had been operated for 20 months. In the HTS cable system, an open type cooling system was constructed for cooling LN2 using as coolant for superconducting cable. The cooling capacity of the cooling system was 6 kW at 69 K. Subcooled LN2 flew thorough 410 m HTS cable, maintaining 69 K of operating temperature for HTS cable. The electric load had fluctuated continuously with the load status so that the cooling state was also controlled to keep stable operating condition. The consumed LN2 used for making subcooled state was refilled periodically, and the amount was 3 tons in average. During all the operating period, the HTS cable system supplied electric power stably without any problem.
更多
查看译文
关键词
Superconducting cables,Cryogenic instrumentation