Reactive Power Limitation Due To Wind-Farm Collector Networks

Jonathon A Martin,Ian A Hiskens

2015 IEEE EINDHOVEN POWERTECH(2015)

引用 27|浏览3
暂无评分
摘要
Type-3 and Type-4 wind turbines are capable of contributing to the reactive power required by wind-farms for supporting grid voltages. However, characterizing the maximum reactive power capability of a wind-farm by summing the individual generator ratings does not account for the effects of voltage variations over the radial collector network and can significantly overestimate the total reactive power production capacity. This paper considers the reactive power produced by a wind-farm in response to a common reactive power set-point Q(set) that is broadcast to all wind turbines. Analysis shows that a sustained increase in Q(set) will result in the wind-farm delivering maximal reactive power. Several examples demonstrate that generator voltage limits can significantly curtail the reactive power output requested by the control strategy. This improved characterization of wind-farm reactive power production capabilities, which takes into account collector network voltages, will enable better design and operation of wind-farm reactive power resources, reducing the need for additional shunt capacitors and static synchronous compensators.
更多
查看译文
关键词
Wind energy integration, reactive power, radial networks
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要