Fault analysis on AC railway supply system

N Noroozi,H Mokhtari,M R Zolghadri,M Khodabandeh, A Abazai, R Seyyedi Khakshani, Samaneh Mazaheri

Power Electronics, Drives Systems & Technologies Conference(2015)

引用 7|浏览2
暂无评分
摘要
A short circuit fault in an AC railway supply system could have undesired consequences; including high-amplitude current flow in the power path, the rail potential rise in the fault vicinity. This paper studies the problem of the rail voltage rise in Tehran-Karaj railway system by the use of a steady state circuit model for the AC autotransformer during a phase-to-ground fault. By using this model, all the currents and voltages of the system can be easily calculated for all possible short circuit fault locations. With the help of the derived analytical model, one can also predict the possible fault locations which may cause the protection system to operate. The estimation of the system currents and voltages levels after the fault helps us to design more effective and economic protection systems and also to estimate the fault location. Transient effects are ignored in the proposed model and the equivalent system represents only the steady state model of the supply system after the fault.
更多
查看译文
关键词
autotransformers,fault location,power system protection,railway electrification,short-circuit currents,ac autotransformer,ac railway supply system,tehran-karaj railway system,economic protection system,fault analysis,phase-to-ground fault,rail voltage,short circuit fault location,steady state circuit model,transient effect,ac railway,atp,fault,steady state