Fitting algorithm for power tower grounding resistance with vertical layered soil model

Lightning Protection(2014)

引用 1|浏览1
暂无评分
摘要
The accurate algorithm, which is used in the calculation of tower grounding resistance of power line in vertical layered soil, is difficult for normal engineering personnel to handle. Based on Green function, the resistance of typical tower grounding device is calculated. Therefore, the fitting function, which represents the relationship between resistivity of vertical layered soil and resistance values of grounding device, is deduced with the hyperbolic function as a fitting function using the least squares curve fitting methods. At last, the fitting formula of tower grounding resistance with the vertical layered soil model is acquired. According to the precision analysis, it is found that the accuracy of proposed formula is related with the initial value, but its maximum error does not exceed 10%.
更多
查看译文
关键词
Green's function methods,curve fitting,earthing,hyperbolic equations,least squares approximations,poles and towers,power cables,Green function,fitting algorithm,hyperbolic function,least squares curve fitting methods,power line,power tower grounding resistance calculation,vertical layered soil model,Green Function,least squares fitting methods,power transmission line,regulation calculation method,tower grounding resistance,vertical layered soil