Uhf Couplers For Gas-Insulated Substations: A Calibration Technique

IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY(1997)

引用 28|浏览1
暂无评分
摘要
Methods that have been used to evaluate the performance of UHF couplers for partial discharge monitoring of gas-insulated substations are briefly reviewed, illustrating the need for a standard test procedure. A measurement scheme is proposed in which the coupler is mounted beneath an aperture in a ground plane and subjected to an incident electric field of known intensity. A TEM line is used to evaluate the technique, and a step excitation is shown to have advantages over swept frequency measurements. The frequency responses of two disc couplers and an external window coupler are measured to demonstrate the technique.
更多
查看译文
关键词
gas-insulated substations, discharge monitoring, wideband UHF couplers
AI 理解论文
溯源树
样例
生成溯源树,研究论文发展脉络
Chat Paper
正在生成论文摘要