Uhf Couplers For Gas-Insulated Substations: A Calibration Technique
IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY(1997)
摘要
Methods that have been used to evaluate the performance of UHF couplers for partial discharge monitoring of gas-insulated substations are briefly reviewed, illustrating the need for a standard test procedure. A measurement scheme is proposed in which the coupler is mounted beneath an aperture in a ground plane and subjected to an incident electric field of known intensity. A TEM line is used to evaluate the technique, and a step excitation is shown to have advantages over swept frequency measurements. The frequency responses of two disc couplers and an external window coupler are measured to demonstrate the technique.
更多查看译文
关键词
gas-insulated substations, discharge monitoring, wideband UHF couplers
AI 理解论文